How to Calculate Cable Size

The Electrical cables play very important role in the transfer of electrical power from one place to another place. For the smooth operation of the electrical power the cable size should be properly selected. This articles teach you how to calculate the proper cable size for a load step by step


Contents

  1. What is Electric Cable
  2. General Electrical Cable Construction
  3. Why Cable Size is Important.
  4. What is proper Cable Size.
  5. Step For Calculating Cable size and Voltage Drop

Button Animation

What is Electric Cable

Electrical cable is a structure composed of one or more conductors enclosed by insulation and some outer protective layers. It's designed to transmit electrical power  or telecommunication signals from one place to another. The conductors are typically made of copper or aluminum.
The Insulation are generally used are PVC (Polyvinyl Chloride), XLPE (cross linked polyethylene) and EPR (ethylene propylene rubber)

Electric Cable

General Electrical Cable Construction

Conductor:  The conductors are typically made of copper or aluminum. Electrical Standard Code for Conductor is : IS: 8130 / IEC 60228/ BS 6360. 

Insulation : It prevents conductor to come in direct contact with each other to cause short circuit. Electrical Standard Codes : IS: 7098, 8130, 14494 / IEC: 60502 / BS: 6622 / BS: 7835.
The Insulation are generally PVC (Polyvinyl Chloride), XLPE (cross linked polyethylene) and EPR (ethylene propylene rubber)

Sheath : It is used for protecting the cable from moistures which would affect the insulation. Cable sheath is made up of lead alloy
Electrical Standard Codes is: BS 6724, IEC 61034, IEC 60754, IEC 60332. 

Bedding: It Provides protection to the metallic sheath from corrosion and  mechanical injury.
It is made up of some fibrous material such as jute or hessian tape.
Electrical Standard Codes : IS: 7098, 1554 / IEC: 60502 / BS: 6622 / BS: 7835

Armouring: Armouring is used to protect the cable from mechanical injury while handling. It consists of one or two layers of galvanized steel wire or steel tape. Armouring is also used for earthing the cable. 
Electrical Standard Codes is:  IS: 7098 / IS: 3975 / IEC: 60502 / BS: 6622/BS: 7835.

Outer Jacket: It is the outer protection part of the cable against the surrounding environment. It provides protection against water ingress, protection against termite, protection against UV and protection against differing soil compositions.
Generally made of PVC
Electrical Standard Codes is : IS: 7098 / IEC: 60502 / BS: 6622/BS: 7835.


Why Cable Size is Important.

Proper cable sizing is important for the safety, reliability, and consistency of an electrical system. It ensures that the system operates efficiently, minimizes voltage drop, and prevents overheating. It also reduces the risk of fire hazards and electrical accidents.

What is proper Cable Size.

The cable size is said to be proper when the cable is able to carry full load current, able to withstand the short circuit current and should have voltage drop within the acceptable limits as per the standards. 

The Permissible Voltage variation of various Transmission and Distribution lines are  given below
1. For LT Lines 
2. For 11KV and 33KV Distribution Lines
3. For Extra high Voltage Lines 

Calculate Cable Size

Let  we have to Select Size of XLPE Cable for the 3 Phase, 415V, 100KW Load. The Load is supplied from Distribution Transformer 11/0.433KV, 250KVA. The Power factor of The load is 0.8. 

Step 1. Find the Load Current

we know that for 3 phase Load 

`P = \sqrt{3}VI_{L}Cos \phi`

Where P = Power Rating of Load in kW
V = Voltage in kilo Volts
`I_{L}` =  Load Current in Amperes
`Cos \phi` = Power Factor of Load

`I_{L} = \frac{P}{\sqrt{3}V cos\phi}`

`I_{L} = \frac{100}{\sqrt{3}\times0.415 \times 0.8}=173.9A`


Step 2: Calculate Short Circuit Current of Transformer

Full load Current of Transformer, `I_{FT}=\frac{P_{T}}{\sqrt{3}\timesV_{T}} = \frac{250}{\sqrt{3}\times 0.433} = 333.34A`

where
`V_{T}` = Voltage on Secondary Side of Transformer
`P_{T}` = Rating of Transformer

Short Circuit Current of Transformer (`I_{sc}`)

`I_{sc} = \frac{I_{T}\times 100}{Z%} = \frac{333.34 \times 100}{4.5}= 7407.56 = 7.407kA`

Where Z% is percentage impedance of Transformer.

Step 3: Calculate Area of Cross section of Cable

Let "A" is Area of cross section of cable in sqmm

`A=\frac{I_{sc}\times \sqrt(t)}{K}`

Where

`I_{sc}` = short circuit of Transformer in Amperes

t = time of short circuit current. it is generally taken 0.14 seconds to 0.2 seconds.
Always remember take it 10 to 20% above the time take by our protective device to trip the circuit from supply in case of fault. 

K = constant, taking account of the resistivity, temperature co-efficient, heat capacity of  the conductor material, initial and final temperature

The table below gives the value of "K"  as per BS 7671 Table 54C 


Putting the values of `I_{sc}`, t and K in above equation

Area of cross section of cable 

`A = \frac{7407.56 \times \sqrt(0.2)}{94.48} = 35sqmm`

Step 4: Check Current Rating of 35sqmm cable from catalogue of Cable provided by manufacture. 

Below the snap of Catalogue of cable from KEI Industries Limited



From the catalogue the current rating of 35sqmm single core cable is 157A.
but our load current is 173.9 A. So 35sqmm cable is not suitable for our load. 

Taking the derating factor (Generally lies between 0.6 to 0.8)  into consideration. Let us take derating factor equal to 0.6

The cable should have current rating (I) equal 




`I =\frac{173.9}{0.6}=289.8A`

So as per the catalogue 95Sqmm cable has current rating 287A which is near to 289.8 A 

So 95Sqmm cable can be used 

Now we will check the voltage drop analysis. Whether the 95Sqmm cable has voltage drop within permissible limit or not


Step : Voltage Drop Analysis 

Voltage drop (`V_{d}`) For 3 Phase

where
`I_{L}` = Load Current
R = Resistance per meter of cable
X = Reactance per meter of Cable

Putin the values of `I_{L}` , R , X and Number of Runs  in the above equation

The Values of R and X can be taken from catalogue
From Catalogue Value of R is 1.110 ohm per meter and X is 0.090 ohm per meter. 

power factor , `cos\phi = 0.8`

let we need 100 meters  to connect the load with power supply

Thus 

`V_{d}=\frac{\sqrt{3}\times 1.2 \times 173.9 \times ((1.110 \times 0.8 )+(0.090 \times 0.6))\times 100}{1000 \times 1} = 19.79 V`

Percentage Voltage drop

`V_{d}% = \frac{V_{d}\times 100}{V_{s}}=\frac{19.79\times100}{415}=4.768%`

For LT Lines The permissible voltage variation is +-6% so that voltage criteria is satisfied 

so the cable size is proper. 

You Can Download the Excel Sheet for Calculation of Cable Size and Voltage Drop Here (Click Here)

For calculation of Cable size Using Etap watch the Video below. 


























Author:

The Author has done B.Tech Electrical Engineering and M.Tech in Electrical Power system Engineering. The author has 11 Years of Industrial Experience in Transmission, Distribution, Substations and Internal Electrification. Presently the author is working in Islamic University of Science and Technology.